2 Design
Wiring for Single-phase Pulse Signal and Direction Signal (d14 = 0)
Connect the single-phase pulse signal or single-phase pulse + direction signal as shown in the dia-
gram below.
• Connect the direction signal to the pulse train input PIA terminal and the single-phase pulse to the
pulse train input PIB terminal.
• The +24 V terminal of the inverter control circuit terminal block is for a 100 mA maximum 24 V pow-
er supply. This terminal can be used for the encoder power supply if the consumption current for the
input terminals in use and the encoder power supply is allowable. However, note that this terminal
must be isolated from any 24 V system power supply for other than the encoder and inverter.
2-56
Encoder
Complementary-output type
encoder
Encoder
Complementary-output type
encoder
Encoder
Complementary-output type
encoder
+24
Vcc
PIB
Out
Direction
PIA
DIC
GND
+24
Vcc
PIB
Out
Direction
PIA
DIC
GND
Source transistor
+24
Vcc
PIB
Out
PIA
Out
Out
PIZ
GND
DIC
M1 Series Standard Type User's Manual (I669)