When a stop is made at the target position with J96 bit 6 = 1, the brake release signal "BRK" is not
turned ON even if the time set at Brake Control Brake-applied Timer (J72) elapses if the RUN com-
mand is ON.
 
When the brake is applied during position control, the motor cannot rotate even if there exists position
error. For this reason, the integral term accumulates which sometimes causes an overload trip to oc-
cur. When ASR integral term cancel "P-SEL" allocated to a multifunction input terminal is turned ON,
the integral term of the speed controller is canceled and P operation is performed.
Parameter
No.
Brake Control Operation
J96
Selection
Input Terminal [DI1] Func-
E01 to E05,
tion Selection to Input Ter-
E98, E99
minal [DI7] Function Se-
lection
J69 Brake Control
Brake-release Frequency
Output frequency
J68 Brake Control
Brake-release Current
Output current
RUN command
"POS-SET"
Brake signal "BRK"
M1 Series Standard Type User's Manual (I669)
Function name
bit 6 = 0: Position control stopped, brake signal OFF (brake applied)
bit 6 = 1: Position control stopped, brake signal ON (brake released)
119: P-SEL (ASR integral term cancellation)
OFF
OFF
OFF
ON
J70: Brake Control
Brake-release Timer
J96 bit6
V/f control
J96 bit 6 = 0
6 Vector Control and Applied Functions
Data
DC injection braking
ON
ON
OFF
J72: Brake Control
J70: Brake Control
Brake-applied Timer
Brake-release Timer
0: Brake signal ON during position control stop
1: Brake signal released during position control stop
Operation time chart
DC injection
braking
OFF
OFF
ON
OFF
J72: Brake Control
Brake-applied Timer
6-59