8 Communications Functions
Parameter No.
H347
H348
H349
H350
H351
H352
H353
H354
E01 to E05, E98,
E99
*1.
Below are the details of the setting target.
ALL: Setting required for all connected inverters
A: Setting required only for management inverter (Station No. 1)
B: Setting required for inverters other than management inverter (Station No. 1)
M: Setting required only for inverters set in H304 to H305 (= Inverters assigned with master role)
*2.
After changing any of the y11 and H303 to H306 data on the management inverter, be sure to cycle the
power supply to apply the changes. For inverters other than the management inverter, these changes will be
applied immediately. However, for inverters other than the management inverter, if y11 is changed to Station
No. 1 (Management Inverter), be sure to cycle the power supply to apply the changes. (Station Nos. 2 to
247 will apply changes immediately.)
*3.
To switch the master inverter among more than one inverter, be sure to set sequential station numbers. If
the set station numbers include any skipped number, communications cannot be established.
*4.
For the management inverter, set the station number to 1 (y11 = 1).
*5.
When the Operation Selection on Communication Error (y12) is set to other than "3: Continue to run" on the
management inverter, the co-inverter communication session will stop if a communications timeout error oc-
curs on the management inverter. In this case, cycle the power supply of the management inverter.
*6.
When Co-Inverter Communication Function Selection (H303) is set to "1: Co-inverter communication" or "2:
Co-inverter communication (Management Inverter)," co-inverter communication will be possible.
*7.
Set these parameters so that H304 is equal to or less than H305.
8-30
Function name
Recipient Register of
All Stations in Co-in-
0000 to FFFF Hex
verter Communica-
tion 3
Sender Register of All
Stations in Co-inver-
0000 to FFFF Hex
ter Communication 3
Recipient Station
Number of All Sta-
1 to 247
tions in Co-inverter
Communication 4
Recipient Register of
All Stations in Co-in-
0000 to FFFF Hex
verter Communica-
tion 4
Sender Register of All
Stations in Co-inver-
0000 to FFFF Hex
ter Communication 4
Recipient Station
Number of All Sta-
1 to 247
tions in Co-inverter
Communication 5
Recipient Register of
All Stations in Co-in-
0000 to FFFF Hex
verter Communica-
tion 5
Sender Register of All
Stations in Co-inver-
0000 to FFFF Hex
ter Communication 5
Input Terminal [DI1]
160: 485 (Start co-inverter
Function Selection to
Input Terminal [DI7]
communication)
Function Selection
Default da-
Data
*10
*10
*8
M1 Series Standard Type User's Manual (I669)
Setting
Unit
ta
*1
target
0000
-
M
0000
-
M
4
-
M
0000
-
M
0000
-
M
5
-
M
0000
-
M
0000
-
M
-
-
A