Omron M1 Series User Manual page 663

Multi-function compact inverter
Hide thumbs Also See for M1 Series:
Table of Contents

Advertisement

 Response
No.
Field name
1
Slave address
2
Function code
3
Number of data bytes
4
Register data 1 (MSB)
5
Register data 1 (LSB)
6
Register data 2 (MSB)
7
Register data 2 (LSB)
8
Register data 3 (MSB)
9
Register data 3 (LSB)
10
Register data 4 (MSB)
11
Register data 4 (LSB)
12
Register data 5 (MSB)
13
Register data 5 (LSB)
14
Register data 6 (MSB)
15
Register data 6 (LSB)
16
Register data 7 (MSB)
17
Register data 7 (LSB)
18
Register data 8 (MSB)
19
Register data 8 (LSB)
20
Register data 9 (MSB)
21
Register data 9 (LSB)
22
Register data 10 (MSB)
23
Register data 10 (LSB)
24
CRC-16 (MSB)
25
CRC-16 (LSB)
*1.
Broadcasting cannot be performed.
*2.
Data as much as the number of data bytes will be transferred. In this example, the inverter sends back
data from 10 holding registers, which is 20 (14 hex) bytes.
8-5-3
Write to Coil [05 hex]
Writes to a single coil. The coil status changes as shown in the table below.
Data
Written data (MSB)
Written data (LSB)
Example) Issuing Forward Run Command to Inverter with Slave
Address 1
You need to set the Run command selection to communications (F02/E102=4).
The coil number for the forward run command is 0001.
M1 Series Standard Type User's Manual (I669)
Example
(hex)
*1
01
03
*2
14
00
0001 hex → 01 dec → OC1 Overcurrent protection (during ac-
celeration)
01
02
201 hex → 1000000001 bin → FW: During forward operation,
ACC: During acceleration
01
00
4D2 hex → 1234 dec → 12.34 [Hz] (Frequency)
00
04
D2
01
012C hex → 300 dec → 3.00 [A] (Current)
2C
0B
0B18 hex → 2840 dec → 284.0 [V] (DC voltage)
18
00
A hex → 10 dec → 10 [hex] (Cumulative running time)
00
00
0A
00
A hex → 10 dec → 10 [hex] (Cumulative operation time)
00
00
0A
F9
14
Coil status
OFF to ON ON to OFF
FF hex
00 hex
00 hex
00 hex
8 Communications Functions
Remarks
8
8-13