Parameter
No.
F42
1st Drive Control Selection/
2nd Drive Control Selec-
tion6-3-1 Sensorless Vector
A14
Control Parameter Settings
on page 6-16
1st Motor Capacity/2nd Mo-
P02/A16
tor Capacity
1st Motor Pole Number/2nd
P01/A05
Manual Torque Boost Volt-
age
1st Motor Rated Current/2nd
P03/A17
Motor Rated Current
1st Motor Armature Resist-
P06/A20
ance/2nd Motor Armature
Resistance
1st Base Frequency/2nd
F04/A02
Base Frequency
1st Rated Voltage at Base
F05/A03
Frequency/2nd Rated Volt-
age at Base Frequency
Magnetic Flux Weakening
d82
Control Function Selection
Magnetic Flux Weakening
d83
Lower Limit
*1.
To enable switching to the 1st and 2nd control, allocate "12: SET (2nd control)" to either of input terminal
[DI1] to [DI7].
6-3-2
Motor Parameter Settings
• Ordinarily, offline auto-tuning is performed to set motor parameters.
However, if offline auto-tuning ends in error, for example, when the inverter does not reach 50% of
its rated current during auto-tuning, set the motor parameters manually.
• To increase the performance of vector control, set each parameter value again according to the mo-
tor in use.
• Obtain the motor's datasheet from the motor manufacturer and set each motor parameter.
For the following set values, set the data for one phase in a Y-connection after conversion in 1st
Base Frequency (F04)/2nd Base Frequency (A02),
1st Motor Armature Resistance (P06)/2nd Mo-
tor Armature Resistance (A20)
M1 Series Standard Type User's Manual (I669)
Function name
0 : IM V/f control
1 : IM Dynamic torque vector control
5 : IM Vector control without speed
sensor
0: IM V/f control
1: IM Dynamic torque vector control
without speed sensor
5: IM Vector control without speed sen-
sor
0.01 to 1000 kW
2 to 128 poles
0.00 to 500.0 A
0.00 to 500.0 A
5.0 to 590.0
80 to 240 V: AVR operation (200 V
class series)
160 to 500 V: AVR operation (400 V
class series)
0: Disable
1: Enable
10 to 70%
6 Vector Control and Applied Functions
Data
:
Set the no-load current of the motor, or set the current
value measured when the motor is in isolated no-load
operation in 1st Base Frequency (F04)/2nd Base Fre-
quency (A02).
Default data
Unit
0
-
Dependent
kW
on capacity
4
Pole
21
A
10.55
A
50.0
Hz
200
V
0
-
40
%
6-17
6