Omron M1 Series User Manual page 616

Multi-function compact inverter
Hide thumbs Also See for M1 Series:
Table of Contents

Advertisement

7 Other Functions
Parameter
No.
J02
J03
J04
J05
J06
J10
J11
J12
J13
J15
J16
J17
J18
J19
J23
J24
J57
7-124
Function name
PID Control PID Command Se-
lection
PID Control P Proportional Gain 0.000 to 30.000
PID Control I Integral Time
PID Control D Differential Time
PID Control Feedback Filter
PID Control Anti-reset Windup
Width
PID Control Select Warning
Output Selection
PID Control Upper Limit of
Warning (AH)
PID Control Lower Limit of
Warning (AL)
PID Control Sleep Frequency
for Process Control
PID Control Sleep Timer for
Process Control
PID Control Restart Frequency
after Stopping for Process Con-
trol
PID Control PID Output Upper
Limit
PID Control PID Output Lower
Limit
PID Control Restart Feedback
Deviation after Stopping for
Process Control
PID Control Restart Delay Time
after Stopping for Process Con-
trol
PID Control Operator PID Ref-
erence Position for Dancer
Data
0:
or
keys on Operator
1: PID process command 1 (Analog
input terminals AI1, AI2(AII),
AI2(AIV))
3: Terminal command UP / DWN con-
trol
4: Communication
0.0 to 3600.0
0.00 to 600.00
0.0 to 900.0
0 to 200
0: Warning from absolute value
1: Warning from absolute value with
hold
2: Warning from absolute value with
latch
3: Warning from absolute value with
hold and latch
4: Warning from PID error
5: Warning from PID error with hold
6: Warning from PID error with latch
7: Warning from PID error with hold
and latch
-100 to 100
-100 to 100
0.0: Disable
1.0 to 590.0
0 to 60
0.0 to 590.0
-150 to 150
999: Depends on setting of F15
-150 to 150
999: Depends on setting of F16
0.0 to 100.0
0 to 3600
-100 to 0 to 100
M1 Series Standard Type User's Manual (I669)
Default
Unit
data
0
-
0.1
time
0
s
0
s
0.5
s
200
%
0
-
100
%
0
%
0
Hz
30
s
0
Hz
999
%
999
%
0
%
0
s
0
%

Hide quick links: