Advertisement

5 Basic Settings
• When E111 = 1, 2, 4, 5, DC braking by the DB terminal operates immediately when the RUN
command turns OFF.
 Forward Rotation Jogging/Reverse Rotation Jogging
• When the FJOG (Forward rotation jogging) terminal or RJOG (Reverse rotation jogging) terminal
is turned ON when the RUN command is OFF, forward rotation or reverse rotation jogging opera-
tion can be performed. Deceleration stop is performed according to the acceleration/deceleration
time regardless of E111.
Fig.: Jogging operation by FJOG and RJOG terminals during an operation stop
FJOG
RJOG
FW
RV
Output
frequency
FJOG, RJOG ON while FW, RV are ON
Fig.: Jogging operation by FJOG and RJOG terminals while inverter is running
• When the FJOG (Forward rotation jogging) terminal and RJOG (Reverse rotation jogging) termi-
nal are both ON, operation is the same as when they are both OFF.
• Operation during a stop follows the setting of Jogging Operation Selection (E111), though the en-
abled/disabled during operation settings are not affected.
• FJOG (Forward rotation jogging) terminal and RJOG (Reverse rotation jogging) terminal are giv-
en priority over jogging operation by the FW terminal/RV terminal and the JG terminal.
5-64
FJOG
RJOG
FW
RV
Output frequency
C20
H54
H55
Mode
Normal
JG
Normal
FJOG, RJOG operation
Normal
Normal
operation
operation
H55
H55
*1
*1
C20
H54
-C20
FJOG priority
RJOG priority
C20
H54
H55
H54
H55
H54
-C20
-C20
JG
Normal
JG
C20
H55
-C20
*1
FJOG, RJOG
H55
simultaneous
operation
Normal
RJOG priority
operation
M1 Series Standard Type User's Manual (I669)
H55
Normal
*1: Acceleration at normal operation
*2: Deceleration at normal operation
*2
H54
H55
*1
*2
Normal
FJOG priority
operation