8 Communications Functions
15
14
BUSY
0
Not used
Operation status
(All bits are ON or active with 1.)
Bit
Symbol
0
FWD
1
REV
2
EXT
3
INT
4
BRK
5
NUV
6
TL
7
VL
Example: Operation Status 1 Monitor (M14) = During forward operation and during acceleration
0000 0010 0000 0001
Data Format [19]: Current Value
A current value is decimal point data (positive), resolution 0.01.
Example: 1st Motor Electronic Thermal Level (F11) = 3.60 A
3.60 ×100 = 360 = 0168 hex →
Data Format [20]: Communications Error Code
Code
1
Non-existent parameter No. specified
2
Non-existent parameter No. specified
3
Improper data (Range error)
7
NAK (Link priority, no right, write disabled)
71
Checksum error, CRC error
72
Parity error
73
Framing error, overrun error, buffer full
Example: Improper address
2 = 0002 hex →
Data Format [21]: Auto Tuning
8-40
13
12
11
10
9
0
RL
ALM
DEC ACC
Description
During forward operation
During reverse operation
Direct DC braking
(or during pre-exciting)
Inverter shut down
During braking
Main circuit DC voltage estab-
lished
(Undervoltage with 0)
Torque limiting
During voltage limiting
= 0401 hex →
04
b
01
68
Hex
Description
00
02
Hex
Hex
8
7
6
5
IL
VL
TL
NUV BRK INT
Operation status
Bit
Symbol
8
IL
9
ACC
10
DEC
11
ALM
12
RL
13
0
14
0
15
BUSY
01
Hex
Hex
Hex
M1 Series Standard Type User's Manual (I669)
4
3
2
1
0
EXT REV FWD
Description
During current limiting
During acceleration
During deceleration
Alarm relay
Communications effective
---
---
During parameter code data
writing