7 Other Functions
Parameter No.
E01 to E05, E98,
E99
S06
W40
Universal DO
When "27: OPO (Option board output)" is allocated to the output terminal, output is performed from the
corresponding output terminal when data is written to the Communication Data Terminal [DO] (S07)
from communication regardless of inverter operation.
Parameter No.
S07
Universal AO
When "10: Universal AO" is allocated to the analog output terminal, output is performed from the ana-
log terminal when data is written to the Communication Data Terminal [AO] (S12) from communication.
Full scale is assumed for a numeric value of 20000.
Parameter No.
F31
S12
7-156
Function name
Input Terminal [DI1] to
[DI7] Function Selec-
25:U-DI (Universal DI)
tion
0000 to FFFF hex
Bit15: RST
Bit14: DI7
Bit13: DI6
Bit6: DI5
Operation command
Bit5: DI4
Bit4: DI3
Bit3: DI2
Bit2: DI1
Bit1: REV
Bit0: FWD
0000 to FFFF hex
Bit12: EN2
Bit11: EN1
Bit6: DI5
Bit5: DI4
Input Terminal Monitor
Bit4: DI3
Bit3: DI2
Bit2: DI1
Bit1: DI7
Bit0: DI6
Function name
Bit8: RO
Communication Data
Bit1: DO2
Terminal [DO]
Bit0: DO1
Function name
Output Terminal [AO]
10: Universal AO
Function Selection
Communication Data
-32,768 to 32,767
Terminal [AO]
(-20,000 = -100%, 20,000 = 100%)
Data
Default data
Data
Default data
Data
Default data
M1 Series Standard Type User's Manual (I669)
Unit
0
-
-
-
-
-
Unit
0
-
Unit
0
-
0
-