6 Vector Control and Applied Functions
Tune the motor pa-
2
rameters while rotat-
ing
Tune the motor %R1
5
and %X while stopped
The tuning result is automatically written to the relevant parameter.
3
Preparing the mechanical system
As preparation for performing rotation tuning, remove machine couplings, and disable safety in-
terlocks.
4
Execution of auto-tuning
1) Set one of 1, 2 or 5 to parameter P04, and press the
Parameter No.
2) Input the RUN command. In the factory default state, forward rotation is performed when
the
command is input via the FW or RV terminals, change the setting of F02.
3) When the RUN command is input, 1, 2 and 5 light and tuning is started with operation stop-
ped. The time required for auto-tuning is approx. 5 to 40 seconds.
4) After (3) above is completed when P04 = 2, acceleration is performed up to 50% of the rat-
ed speed and rotation tuning is started. When rotation tuning is completed, a deceleration
stop is performed. The time required for this operation is 10 seconds excluding the acceler-
ation/deceleration time.
5) When the RUN command via the FW and RV terminals is selected according to the F02 = 1
setting, tuning is completed when
6-66
P04/A18 data
Data to be tuned
No-load current (P06/
A20)
Primary resistance
%R1 (P07/A21)
Leakage reactance
%X (P08/A22)
Rated slip (P12/A26)
Magnetic saturation
factor 1 to 5 (P16/
A20)
%X correction factor
(P53/A53)
Primary resistance
%R1 (P07/A21)
Leakage reactance
%X (P08/A22)
%X correction factor
(P53/A53)
Function name
1st Auto Tuning Function
Selection
P04
key is pressed in an enabled state. To perform reverse rotation or when the RUN
Tuning
Tuning is performed in
the following order.
%R1, %X in motor
stopped state
No-load current and
magnetic saturation
factor in motor ro-
tating state (50% of
base frequency)
Rated slip in motor
stopped state again
Tuning is performed in
a stop state.
key. 1, 2 and 5 blink slowly.
Data
1: Tune the motor parame-
ters while stopped
2: Tune the motor parame-
ters while rotating
5: Tune the motor %R1 and
%X while stopped
is displayed. Turn the RUN command OFF. When
M1 Series Standard Type User's Manual (I669)
Supplementary ex-
planation
When the motor can
be rotated safely.
When the motor can-
not be rotated. (Ap-
plied only when rota-
tion tuning has been
performed and the wir-
ing length has been
changed)
Default
Unit
data
0
-