5-4

RUN command

5-4-1

RUN Command Selection

Select the input method for the RUN command.
Parame-
Function name
ter No.
1st RUN Command
Selection
F02
2nd RUN Command
E102
Selection
*1
Related functions
*1.
To enable switching to the 1st and 2nd control, allocate "12: SET (2nd control)" to either of input terminal
[DI1] to [DI7].
*2.
When "4: RS-485 communication" is selected at 1st RUN Command Selection (F02)/2nd RUN Command
Selection (E102), the FW command is executed by setting bit 0 of Operation command (S06) to ON, and the
RV command is executed by setting bit 1 to ON. These parameters are exclusively for reading and writing
via the RS-485 interface. These parameters are not displayed on the Operator. To check these parameters,
use Sysmac Studio.
The operation method for data selected at 1st RUN Command Selection (F02)/2nd RUN Command
Selection (E102) is as follows.
Data
When the
0
nal turns ON. Reverse rotation is performed when the RV terminal turns ON. When the
pressed, operation is stopped.
Forward rotation is performed when the FW terminal turns ON regardless of the
1
Operator. Reverse rotation is performed when the RV terminal turns ON. Operation stops when
both the FW and RV terminals are OFF or both are ON.
When the
2
pressed, operation is stopped.
When the
3
pressed, operation is stopped.
When bit 00:FW in Operation command (S06) is turned ON via RS-485 communication, forward
4
rotation is performed. When bit 01:RV is turned ON, reverse rotation is performed. When both are
OFF or ON, operation is stopped.
• When "0: Operator (Direction of rotation input: terminal block)" and "1: External signal (Digital input)"
are selected at RUN Command Selection (F02/E102), allocate "98: FW (forward rotation)" and "99:
RV (reverse rotation)" to each of Input Terminal [DI6] Function Selection (E98) and Input Terminal
M1 Series Standard Type User's Manual (I669)
0 to 5
0: Operator (Direction of rotation input: terminal
block)
1: External signal (FW or RV)
2: Operator (Forward rotation)
3: Operator (Reverse rotation)
4: RS-485 communication
5: Do not use
Input Terminal [DI6] Function Selection (E98), Input Terminal [DI7] Func-
tion Selection (E99)
Refer to 5-9-1 Input Terminal Functions on page 5-51.
Operation command (S06)
Operation method
key on the Operator is pressed, forward rotation is performed when the FW termi-
key on the Operator is pressed, forward rotation is performed. When the
key on the Operator is pressed, reverse rotation is performed. When the
Data
*2
5 Basic Settings
Default
Unit
data
2
-
5
key is
key on the
key is
key is
5-25