Omron M1 Series User Manual page 618

Multi-function compact inverter
Hide thumbs Also See for M1 Series:
Table of Contents

Advertisement

7 Other Functions
Parameter
No.
*1
W132
E01 to E05,
E98, E99
E20, E21, E27
E61, E62, E63
Related function
*1.
It can be referenced or set only from the communications function or Sysmac Studio.
*2.
The OFF delay of the Under sleep mode of PID control (44: PID-STP) terminal becomes the time obtained
by adding 0.1 s to Output Terminal [DO1] OFF Delay Time (H310), Output Terminal [DO2] OFF Delay Time
(H312) and Output Terminal [ROA, ROB] OFF Delay Time (H314).
PID Control Function Selection
PID control is enabled by setting other than 0 to PID Control Function Selection (J01).
• PID Control Function Selection (J01) = "1: Process normal operation," "2: Process inverse opera-
tion"
If the PID process control is performed and PID calculation results are negative, the frequency refer-
ence to the inverter is limited at 0 Hz.
• PID Control Function Selection (J01) = "4: Process normal operation, opposite operation available,"
"5: Process inverse operation, opposite operation available"
If the PID process control is performed and PID calculation results are negative, an opposite opera-
tion can be performed for the inverter. PID Control PID Output Variable Range for Process Control
(E120) is disabled.
• PID Control Function Selection (J01) = "3: Dancer"
PID dancer control is performed. Opposite operation can be done for dancer control.
7-126
Function name
PID Control PID Deviation (No
Scale Transformation)
Input Terminal [DI1] to [DI7]
Function Selection
Output Terminal [DO1] Function
Selection, Output Terminal
[DO2] Function Selection, Out-
put Terminal [ROA, ROB] Func-
tion Selection
Input Terminal [AI2] Function
Selection (AII) (E62)/Input Ter-
minal [AI2] Function Selection
(AIV) (E63)
Data
-32768 to 32767
-20000 = -100%
+20000 = +100%
20: PID (PID control cancellation)
21: IVS (Normal/Inverse switching)
33: PID-RST (Switch normal/inverse
operation)
34: PID-HLD (Hold PID integral com-
ponent hold)
171: PID-SS1 (PID control multistage
command 1)
172: PID-SS2 (PID control multistage
command 2)
42: OD (Excessive PID deviation)
43: PID-CTL (Under PID control)
44: PID-STP (Under sleep mode of
*2
PID control)
186: FBV (PID FB status output)
21 : PID feed forward
Output Terminal [DO1] ON Delay Time (H309)
Output Terminal [DO2] ON Delay Time (H311)
Output Terminal [ROA, ROB] ON Delay Time (H313)
Output Terminal[DO1] OFF Delay Time (H310)
Output Terminal[DO2] OFF Delay Time (H312)
Output Terminal [ROA, ROB] OFF Delay Time (H314)
M1 Series Standard Type User's Manual (I669)