Set frequency (1) + E30
Set frequency (1) - E30
Set frequency (2) + E30
Set frequency (2) - E30
Frequency arrival signal 1
(constant speed) "FAR1"
Frequency arrival signal 2 "FAR2"
Over Set Frequency Arrival Signal (E20, E21, E27 = 2: FDT1, 31:
FDT2)
An ON signal is output when the output frequency becomes equal to or higher than the operation level
(E31/E36) set in the frequency detection, and the signal is turned OFF when the frequency falls below
Frequency Detection Hysteresis Width (FDT1/ FDT2) (E32).
Name
Over set frequency ar-
rival signal 1
Over set frequency ar-
rival signal 2
Over set frequency
arrival signal 1 "FDT1"
Over set frequency
arrival signal 2 "FDT2"
Set-frequency-only Arrival Signal (E20, E21, E27 = 183: FDT3, 185:
FDT4)
An ON signal is output when the output frequency is within the range of the operation level (E31/E36)
set in the frequency detection, and the signal is turned OFF when the frequency is out of range.
M1 Series Standard Type User's Manual (I669)
Frequency settings
Set frequency (1)
Set frequency (2)
Frequency Arrival 2 ON Timer E29
E20, E21, E27
Output signal
allocated data
FDT1
FDT2
Output frequency
Frequency settings changed
Output frequency
ON
Frequency
Arrival 2
ON Timer
ON
E29
Operation level
Range: 0.0 to 500.0
Hz
2
E31
31
E36
Frequency Detection
Set frequency
Level1 (FDT1/FDT3) (E31),
Frequency Detection Level 2
(FDT2/FDT4) (FDT1/FDT3) (E36)
Frequency Detection Hysteresis
Width (FDT1/ FDT2) (E32)
Cancellation level
ON
7 Other Functions
ON
ON
Hysteresis width
Range: 0.0 to 500.0
Hz
E32
E32
Time
Time
7-91
7