Three-phase 200 V full capacity
Three-phase 400 V full capacity
Single-phase 200 V (2.2 k or less)
Single-phase 200 V (3.7 kW)
• For loads (such as fans and pumps) that do not require frequent use of the inverter above the rated
torque, the light load mode can be selected. The rated current of the inverter increases above that of
the heavy load mode, which enables the inverter to drive a motor one size larger. For details on rat-
ed current specifications, refer to 1-3-1 Standard Specifications on page 1-11. The overload capacity
differs as shown in the following table on each specification type.
F80 data
0
3
(only for 400 V)
1
4
(only for 400 V)
Related Parameters
• Some parameters are restricted by changing the setting of Load Mode Selection (F80).
 When Drive Control Selection (F42/A14) = 0 to 6 (induction motor)
• The set values of the following parameters are overwritten with the following values according to
the new settings after changing Load Mode Selection (F80).
• Manual Torque Boost Voltage (F09/A05), Overload Protect Level (F44/E147)
• The upper limit values of the following parameters change according to the new settings after
changing Load Mode Selection (F80). When the set values exceed the upper limit, they are over-
written with the upper limit.
• Carrier Frequency (F26), DC Injection Braking Level (F21/A10)
M1 Series Standard Type User's Manual (I669)
HHD
F80 = 0
OK
OK
OK
OK
Specification type
HHD
Heavy load mode
HD
HND
Light load mode
HD
HND
HD
F80=1
F80=3
OK
-
OK
OK
OK
-
-
-
Continuous rated cur-
rent level
Motor of same capacity
as inverter capacity can
be driven
Motor of capacity one size
larger than the inverter
capacity can be driven
Motor of capacity one size
larger than the inverter
capacity can be driven
Motor of capacity one to
two sizes larger than the
inverter capacity can be
driven
5 Basic Settings
ND
F80=4
-
OK
-
-
Ambient
Overload
tempera-
capacity
ture
150% 1 min
Up to 50°C
200% 0.5 s
Up to 40°C
150% 1 min
Up to 50°C
120% 1 min
Up to 40°C
120% 1 min
5-13