Omron M1 Series User Manual page 517

Multi-function compact inverter
Hide thumbs Also See for M1 Series:
Table of Contents

Advertisement

Item
Parameter
No.
No.
6_06
X159
6_07
X153
6_09
X154
6_30
X158
Running Status 3 Monitor [6_24]
The operation status 3 displays the status allocated to each bit by a four-digit hexadecimal.
The allocation for 0 to 15 bits of the operation status is described in the table below.
Bit Symbol
15
-
Fixed to 0
14
ID2
Current detection 2
13
IDL
Low current detection
12
ID
Current detection
11
OLP
During active drive
10
LIFE
Life warning
9
OH
Heat sink overheat early warning
8
TRY
During retry
7
FAN
Fan operation signal
6
KP
During touch panel operation
5
OL
Motor overload early warning
4
IPF
During restart after instantaneous power failure
3
SWM2
Motor 2 selection
2
RDY
During operation preparation
1
FDT
Frequency detection
0
FAR
Frequency arrival
M1 Series Standard Type User's Manual (I669)
Item
Fifth Last Alarm Info.
0000Hex to
Running Status
FFFFHex
Fifth Last Alarm Info.
Cumulative Ope.
0 to 655,350 hours
Time
Fifth last Alarm Info.
Main Circuit DC Volt-
0.0 to 999.0 [V]
age
Fifth last Alarm Info.
Cumulative Running
0 to 655,350 hours
time
Description
Range
The operation status is displayed by a
four-digit hexadecimal.
The number of operations of the motor
(number of times the RUN command for
the inverter is turned ON) is calculated
and displayed.
The Main Circuit DC Voltage of the inver-
ter is displayed.
The cumulative time of the inverter RUN
state is displayed.
The cumulative operation time is dis-
played alternately in the upper digits and
lower digits.
When the lower three digits are dis-
played, an h (hours) is displayed in the
lowermost digit.
7 Other Functions
Description
7-25