General technical data
8.2 EMC compatibility, shipping and storage conditions
Sinusoidal disturbance variables
The table below shows the electromagnetic compatibility of the ET 200eco PN distributed I/O
device with respect to sinusoidal disturbances.
80 to 1000 MHz; 1.4 to 2 GHz
10 V/m 80% AM (1 kHz)
2 to 2.7 GHz
1 V/m at 80 % AM (1 kHz)
Emission of radio interference
Interference emission of electromagnetic fields in accordance with EN 61000-4-6: (measured
at a distance of 10 m).
Frequency
30 MHz to 230 MHz
230 MHz to 1000 MHz
Shipping and storage conditions
The ET 200eco PN distributed I/O device surpasses the requirements according to IEC 61131-2
for transport and storage conditions. The following information applies to modules
transported or stored in their original packaging.
Type of condition
Free fall
Temperature
Temperature change
Air pressure
Relative humidity
98
HF radiation according to IEC 61000-4-3
Electromagnetic HF field
Amplitude modulated
HF coupling according to
IEC 61000-4-6
0.15 MHz to 80 MHz
10 V
unmodulated
rms
80 % AM (1 kHz)
150 Ω source impedance
Noise emission
< 40 dB (µV/m)Q
<47 dB (µV/m) Q
Permissible range
≤ 0.3 m
from -40 °C to +70 °C
20 K/h
From 1140 hPa to 660 hPa
(corresponds with an altitude of -1000 m to
3500 m)
From 5% to 95%, without condensation
Operating Instructions, 06/2022, A5E01250250-AN