I/O device digital inputs/digital outputs
9.2 I/O device digital outputs
Technical data
Bus protocol
Supported Ethernet services
PROFINET interface
Connection socket
Switch function
Auto-crossover
Manufacturer ID (Vendor ID)
Device ID (DeviceID)
Voltages and currents
Supply voltage 1L+
Reverse polarity protection
Infeed current 1L+
Supply voltage 2L+
Reverse polarity protection
Infeed current 2L+
Total current of the outputs *
All mounting positions to 60°C
Current consumption
From supply voltage (1L+)
From supply voltage (2L+)
Power loss of the device
Digital outputs
Number of outputs
Insulation
Insulation test voltage
Ethernet interface
All other circuit elements
Electrical isolation
Between 1L+ and 2L+
Between 1L+, channels and all other circuit ele­
ments
Between channels
140
PROFINET IO
IRT with the option "high flexibility"
IRT with the option "high performance"
PROFINET IO (Device)
ping
arp
LLDP
Network diagnostics (SNMP)
DCP
Prioritized startup
Media redundancy
2 x M12 d-coded
Yes, internal
Yes, if autonegotiation is enabled
002A
H
0306
H
DC 24 V
Yes, against destruction, loads are activated
Max. 4 A
DC 24 V
Yes, against destruction, loads are activated
Max. 4 A
Max. 3.9 A per 1L+ and 2L+
Typ. 100 mA
Typ. 5 mA
Typ. 5.5 W
16
1500 V
(IEEE802.3, Type Test)
rms
707 V DC (type test)
Yes
No
No