I/O device analog input/analog output
10.1 I/O device analog input
Technical specifications
Insulation
Insulation test voltage
Ethernet interface
All other circuit elements
Standards, approvals, certificates
Suitable for applications according to AMS 2750
Suitable for applications according to CQI-9
Electrical isolation
Between 1L+ and 2L+
Between 1L+, channels and all other circuit ele­
ments
Between channels
Between Ethernet and all other circuit elements Yes
1
"No temperature compensation" is always run when using the measuring type ±80 mV regardless of
the configured temperature compensation.
2
With 3-wire resistance measurement (and thermal resistor) the measuring resistances and the line
resistances are updated in alternating cycles. Rapid changes in the measuring resistance therefore
impair the accuracy.
3
For thermocouples, the information refers to the temperature range from -100 °C to nominal value.
NOTE
The accuracy information is valid for static thermal states and changes in ambient temperat­
ure < 1 K/h.
The I/O device achieves the highest accuracy with the 4-wire connection system (see technic­
al specifications above).
Although the 3-wire connection system compensates for the missing wire, the accuracy is
impaired. With the 2-wire connection system, the line resistances considerably impair the
accuracy.
In the last two cases this impairment is not determinable.
NOTE
With the 3-wire connection system, the compensation of the missing cable is only ensured if
all three cores in the cable have the same length and cross-section.
166
1500 V
(IEEE802.3, Type Test)
rms
707 V DC (type test)
Yes; Declaration of Conformity, see online support
entry 109757262
Yes; based on AMS 2750 E
Yes
No
No