UKCA mark
The ET 200eco PN distributed I/O system complies with the designated British standards (BS)
for programmable logic controllers published in the official consolidated list of the British
Government. The ET 200eco PN distributed I/O system meets the requirements and
protection targets of the following regulations and related amendments:
• Electromagnetic Compatibility Regulations 2016 (EMC)
• Equipment and Protective Systems Intended for use in Potentially Explosive Atmospheres
Regulations 2016 (Explosion Protection)
• The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic
Equipment Regulations 2012 (RoHS).
UK declarations of conformity for the respective authorities are available from:
Siemens AG
Digital Industries
Factory Automation
DI FA TI COS TT
P.O. Box 1963
D-92209 Amberg
The UK declarations of conformity are also available for download from the Siemens Industry
Online Support website, under the keyword "Declaration of Conformity".
ATEX approval
According to EN 60079-15 (Electrical apparatus for potentially explosive atmospheres - Part
15: Type of protection "n"), EN 60079-0 (Electrical apparatus for potentially explosive gas
atmospheres - Part 0: General Requirements) and EN 60079-31 (Equipment dust ignition
protection by enclosure "t").
II 3 G Ex nA IIC T4 Gc
II 3 D Ex tc IIIC T90°C Dc
DEKRA 12ATEX0220 X
OR
According to EN IEC 60079-7 (Electrical apparatus for potentially explosive atmospheres - Part
7: Increased safety "e"), EN IEC 60079-0 (Electrical apparatus for potentially explosive gas
atmospheres - Part 0: General Requirements) and EN 60079-31 (Electrical apparatus for
potentially explosive atmospheres – Part 31: dust ignition protection by enclosure "t").
II 3 G Ex ec IIC T4 Gc
II 3 D Ex tc IIIC T90°C Dc
DEKRA 20ATEX0119 X
Special conditions in hazardous areas:
Install the device so that there is a minimal risk of mechanical danger.
To prevent electrostatic charging, wipe the housing surface only with a wet cloth.
Use the device only in an environment that is protected from UV light.
The following additional conditions apply when using the devices in an area that requires EPL
Gc:
• Only use the device in an area with a degree of pollution 2 according to EN 60664-1.
• Provisions must be taken to prevent the rated voltage from being exceeded by transient
disturbance voltages of more than 119 V.