Siemens SIMATIC Distributed I/O ET 200eco PN Operating Instructions Manual page 147

Hide thumbs Also See for SIMATIC Distributed I/O ET 200eco PN:
Table of Contents

Advertisement

I/O device digital inputs/digital outputs
9.3 I/O device digital inputs/digital outputs
Technical data
Input delay
At "0" to "1"
At "1" to "0"
Input characteristic
Connection of 2-wire proximity switches
Permitted quiescent current
Actuator selection data
Cable length, shielded
Cable length, unshielded
Output voltage
Nominal value
For signal "1"
Output current
At signal "1"
For "0" signal (residual current)
Load resistance range
Lamp load
Parallel wiring of two outputs
To increase performance
For redundant control of a load
Control of a digital input
Switching frequency
With resistive load
With inductive load
With lamp load
Limiting of the inductive shutdown voltage to lamp
load
Short-circuit protection of the output
Response threshold
148
Typ. 3 ms
Typ. 3 ms
According to IEC 61131, Type 3
Supported
Max. 1.5 mA
Max. 30 m
Max. 30 m
24 V DC
Min. 1L+/2L+ (-0.8 V)
Max. 1.3 A
Max. 1.5 mA
22 Ω to 3.3 kΩ
Max. 5 W
No
Supported
Yes
Max. 100 Hz
Max. 0.5 Hz
Max. 1 Hz
Typ. 1L+/2L+ (-47 V)
Yes, electronic
Typ. 1.8 A (per channel)
Operating Instructions, 06/2022, A5E01250250-AN
ET 200eco PN

Advertisement

Table of Contents
loading