I/O device digital inputs/digital outputs
9.3 I/O device digital inputs/digital outputs
Technical data
Input delay
•
At "0" to "1"
•
At "1" to "0"
Input characteristic
Connection of 2-wire proximity switches
•
Permitted quiescent current
Actuator selection data
Cable length, shielded
Cable length, unshielded
Output voltage
•
Nominal value
•
For signal "1"
Output current
•
At signal "1"
•
For "0" signal (residual current)
Load resistance range
Lamp load
Parallel wiring of two outputs
•
To increase performance
•
For redundant control of a load
Control of a digital input
Switching frequency
•
With resistive load
•
With inductive load
•
With lamp load
Limiting of the inductive shutdown voltage to lamp
load
Short-circuit protection of the output
•
Response threshold
148
Typ. 3 ms
Typ. 3 ms
According to IEC 61131, Type 3
Supported
Max. 1.5 mA
Max. 30 m
Max. 30 m
24 V DC
Min. 1L+/2L+ (-0.8 V)
Max. 1.3 A
Max. 1.5 mA
22 Ω to 3.3 kΩ
Max. 5 W
No
Supported
Yes
Max. 100 Hz
Max. 0.5 Hz
Max. 1 Hz
Typ. 1L+/2L+ (-47 V)
Yes, electronic
Typ. 1.8 A (per channel)
Operating Instructions, 06/2022, A5E01250250-AN
ET 200eco PN