Parameter Overview Digital Inputs - Siemens SIMATIC Distributed I/O ET 200eco PN Operating Instructions Manual

Hide thumbs Also See for SIMATIC Distributed I/O ET 200eco PN:
Table of Contents

Advertisement

Technical data
At "0" to "1"
At "1" to "0"
Input characteristic
Connection of 2-wire proximity switches
Permitted quiescent current
9.1.4

Parameter overview digital inputs

Parameters for 8 DI DC 24V 4×M12 (6ES7141-6BF00-0AB0) and for 8 DI DC 24V 8×M12
(6ES7141-6BG00-0AB0)
Parameter
Group diagnostics
Diagnostics: Missing 1L+
Diagnostics: Wire break at inputs 0 to 7
(channels 0 to 7)
Diagnostics: Short-circuit to M, inputs
0,4/1,5/2,6/3,7 (channels 0,4/1,5/2,6/3,7)
Parameters for 16 DI DC 24V 8×M12 (6ES7141-6BH00-0AB0)
Parameter
Group diagnostics
Diagnostics: Missing 1L+
Diagnostics: Wire break at inputs 0 to 15
(channels 0 to 15)
Diagnostics: Short-circuit to M, inputs
0,8/1,9/2,10/3,11/4,12/5,13/6,14/7,15
(channels
0,8/1,9/2,10/3,11/4,12/5,13/6,14/7,15)
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Typ. 3 ms
Typ. 3 ms
According to IEC 61131, Type 3
Supported
Max. 1.5 mA
Range of values
Default setting
Disable
Disable
Enable
Disable
Disable
Enable
Disable
Disable
Enable
Disable
Disable
Enable
Range of values
Default setting
Disable
Disable
Enable
Disable
Disable
Enable
Disable
Disable
Enable
Disable
Disable
Enable
I/O device digital inputs/digital outputs
9.1 I/O device digital inputs
Range of effectiveness
Device
Device
Channel
Channel group
Range of effectiveness
Device
Device
Channel
Channel group
121

Advertisement

Table of Contents
loading

Table of Contents