4.3 Device names for ET 200eco PN

Configuring the submodule of the IO-Link master
Requirements
• You have configured your automation system.
• In the device configuration of the 6ES7148-6JD00-0AB0 IO-Link Master, you have selected
the IO-Link port that you want to configure.
Procedure
1. You configure the operating mode of the submodule. An overview of possible operating
modes is available in the chapter Configuration (Page 213).
2. When you have configured the submodule and thus defined the operating mode, make
the additional settings:
• Enable the Autostart parameter (without S7-PCT)
NOTE
Changes to the port configuration
If you have assigned the parameters for the IO-Link device via Autostart (without S7-PCT),
or have configured the port as digital input, digital output or disabled, you can no longer
change the port configuration via S7-PCT.
• Enabling the diagnostics (only in IO-Link mode)
• Enable the parameter assignment for the hardware interrupts (only in IO-Link mode)
Response after "Resetting the IO-Link settings" via S7-PCT
• Deleting the IO-Link device data in the backup memory or the IO-Link Master
• Resetting the parameters to factory state:
– Resetting the inspection severity and the backup behavior
NOTE
Effects on the device configuration
If you have reset the IO-Link settings via S7-PCT, you have to reload the device configura­
tion via S7-PCT.
4.3
Device names for ET 200eco PN
Introduction
Every PROFINET IO device is assigned a unique device ID (MAC address) before it leaves the
factory.
Each ET 200eco PN IO Device is addressed based on its device name during configuration and
in the user program.
66
Operating Instructions, 06/2022, A5E01250250-AN
ET 200eco PN