Technical specifications
•
Current
•
Resistor and thermal resistor
•
Thermocouple
Permitted input voltage for voltage input (destruc
tion limit)
Connection of sensors for voltage measurement
Connection of sensors for current measurement
Connection of sensors for RTD
Connection of sensors for thermocouples
Temperature compensation for thermocouples
•
Internal temperature compensation
•
External temperature compensation
Technical unit for temperature measurement
Formation of analog values
Measuring principle
Integration time and conversion time/resolution (per channel)
•
Integration time parameterizable
•
Interference frequency suppression in Hz
•
Integration time in ms
•
Conversion time in ms (per channel)
•
Resolution for voltage (including overrange)
•
Resolution for current (including overrange)
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
I/O device analog input/analog output
±20 mA/17 V for 2-wire transducer, 3.5 V for
4-wire transducer
0 to 20 mA/17 V for 2-wire transducer, 3.5 V for
4-wire transducer
4 to 20 mA/17 V for 2-wire transducer, 3.5 V for
4-wire transducer
150 Ω/10 MΩ
300 Ω/10 MΩ
600 Ω/10 MΩ
3000 Ω/10 MΩ
Ni100/10 MΩ
Ni1000/10 MΩ
Ni120/10 MΩ
Ni200/10 MΩ
Ni500/10 MΩ
Pt100/10 MΩ
Pt1000/10 MΩ
Pt200/10 MΩ
Pt500/10 MΩ
Types E, J, K, N
28.8 V continuous, 35 V for max. duration of
500 ms
Yes
Yes (as 2-wire/4-wire transducer)
Yes (with 2-/3-/4-conductor connection)
Yes
1
Yes, parameterizable
Yes, parameterizable
°C, °F, K
Integrating
Yes
500/60/50/10
2.0/16.667/20/100
2
4/19/22/102
±80 mV/15 bps + sign
±10 V/15 bps + sign
0 to 10 V/15 bps
1 to 5 V/15 bps
±20 mA/15 bps + sign
0 to 20 mA/15 bps
4 to 20 mA/15 bps
10.1 I/O device analog input
155