Technical data
Interrupts
Diagnostics function
•
Group error/maintenance
•
Bus monitoring PROFINET IO
•
Monitoring of supply voltage 1L+
•
Monitoring of supply voltage 2L+
•
Existing connection to network
•
Digital output
•
Fault at digital output
•
Diagnostic information can be read
Monitoring for
•
Failures of 2L+
•
Short-circuit
•
Wire break
Actuator selection data
Cable length, shielded
Cable length, unshielded
Output voltage
•
Nominal value
•
For signal "1"
Output current
•
At signal "1"
•
For "0" signal (residual current)
Load resistance range
Lamp load
Parallel wiring of two outputs
•
To increase performance
•
For redundant control of a load
Control of a digital input
Switching frequency
•
With resistive load
•
With inductive load
•
With lamp load
Limiting of the inductive shutdown voltage to lamp
load
Short-circuit protection of the output
•
Response threshold
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
I/O device digital inputs/digital outputs
9.2 I/O device digital outputs
Yes
Yes
Red/yellow "SF/MT" LED
Red "BF" LED
Green "ON" LED
Green "DC24V" LED
Green LED "P1 LK" and "P2 LK";
Green LED
Red LED
Yes
Yes
Yes
Yes, in the off state, per channel
Max. 30 m
Max. 30 m
DC 24 V
Min. 1L+/2L+ (-0.8 V)
0.5 A
Max. 1.5 mA
48 Ω to 3.3 kΩ
Max. 5 W
No
Supported
Yes
Max. 100 Hz
Max. 0.5 Hz
Max. 1 Hz
Typ. 1L+/2L+ (-47 V)
Yes, electronic
Typ. 0.7 A (per channel)
129