Siemens SIMATIC Distributed I/O ET 200eco PN Operating Instructions Manual page 128

Hide thumbs Also See for SIMATIC Distributed I/O ET 200eco PN:
Table of Contents

Advertisement

Technical data
Interrupts
Diagnostics function
Group error/maintenance
Bus monitoring PROFINET IO
Monitoring of supply voltage 1L+
Monitoring of supply voltage 2L+
Existing connection to network
Digital output
Fault at digital output
Diagnostic information can be read
Monitoring for
Failures of 2L+
Short-circuit
Wire break
Actuator selection data
Cable length, shielded
Cable length, unshielded
Output voltage
Nominal value
For signal "1"
Output current
At signal "1"
For "0" signal (residual current)
Load resistance range
Lamp load
Parallel wiring of two outputs
To increase performance
For redundant control of a load
Control of a digital input
Switching frequency
With resistive load
With inductive load
With lamp load
Limiting of the inductive shutdown voltage to lamp
load
Short-circuit protection of the output
Response threshold
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
I/O device digital inputs/digital outputs
9.2 I/O device digital outputs
Yes
Yes
Red/yellow "SF/MT" LED
Red "BF" LED
Green "ON" LED
Green "DC24V" LED
Green LED "P1 LK" and "P2 LK";
Green LED
Red LED
Yes
Yes
Yes
Yes, in the off state, per channel
Max. 30 m
Max. 30 m
DC 24 V
Min. 1L+/2L+ (-0.8 V)
0.5 A
Max. 1.5 mA
48 Ω to 3.3 kΩ
Max. 5 W
No
Supported
Yes
Max. 100 Hz
Max. 0.5 Hz
Max. 1 Hz
Typ. 1L+/2L+ (-47 V)
Yes, electronic
Typ. 0.7 A (per channel)
129

Advertisement

Table of Contents
loading

Table of Contents