Error class
Error text
00111
7
Overflow
B
D
01000
8
Underflow
B
D
01001
9
Error
B
D
10000
16
Parameter assign­
B
D
ment errors
10010
18
Fuse defective
B
D
11010
26
External error
B
D
Errors types IO-Link Master (6ES7148-6JD00-0AB0)
IO-Link devices diagnostics
The IO-Link master generates PROFINET channel diagnostics (CET, ECET) from the IO-Link
events of an IO-Link devices according to the following mapping rules:
The IO-Link event codes of the area 0x0000 – 0x7FFF
Device Diagnostics - Page 1" (CET 0x9500
ECET
The IO-Link event codes of the area 0x8000 – 0xFFFF
Device Diagnostics - Page 2" (CET 0x9501
ECET
Table 7-10  Overview Error types IO-Link Device Diagnostics
IO-Link Event
Error type
Code
(CET)
0x0000 - 0x7FFF
0x9500
H
(38144
0x8000 - 0xFFFF
0x9501
H
(38134
Example of Display of IO-Link Event Codes:
An IO-Link device supports the event codes 0x4000
The channel diagnostics result from the event codes:
• CET: 0x9500
Diagnostic alarm "IO-Link Device Diagnostics - Page 1, Temperature fault - Overload",
generates Event Code 0x4000
• CET: 0x9501
Diagnostic alarm "IO-Link Device Diagnostics - Page 2, Ambient light interference,
generates Event Code 0x8CA0
IO-Link Port Diagnostics
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Meaning
Process variable range exceeded (0x8C10)
Measuring range exceeded (0x8C20)
Process variable range too small (0x8C30)
All the IO-Link error codes not listed here will be mapped to this
PROFINET IO error.
Hardware error at IO-Link Master detected
IO-Link Master could not be parameterized
Event code of the IO-Link Device (0x6230 to 0x6340)
Event code of the IO-Link Device (0x5450 to 0x5459)
IO-Link Device cannot be set to desired mode
= IO-Link Event Code
H
H
= (IO-Link Event Code
H
H
Expanded error type
(ECET)
0x0000 - 0x7FFF
H
)
(0 - 32767
)
D
D
0x0000 - 0x7FFF
H
)
(0 - 32767
)
D
D
, ECET: 0x4000
H
, ECET: 0xCA0
H
):
H
) via the following rule:
H
– 0x8000
)
H
Error text
Error / Warn­
H
ing
Error / Warn­
H
ing
H
H
from the IO-Link.
H
H
from the IO-Link.
H
Interrupt, error, and system messages
7.5 Diagnostics with STEP 7
IO-Link
Master
are displayed directly in the "IO-Link
H
are displayed directly in the "IO-Link
H
Meaning
See manual of the IO-Link devices or IODD
file used.
See manual of the IO-Link devices or IODD
file used.
and 0x8CA0
.
H
IO-Link
Device
X
X
X
X
X
X
X
X
89