Technical data
Between 1L+, channels and all other circuit ele­
ments
Between channels
Between Ethernet and all other circuit elements Yes
Status, interrupts, diagnostics
Interrupts
Diagnostics function
Group error/maintenance
Bus monitoring PROFINET IO
Monitoring of supply voltage 1L+
Existing connection to network
Digital input
Fault at digital input
Digital output
Fault at digital output
Diagnostic information can be read
Monitoring for
Failure of 1L+ and 2L+
Sensor supply short-circuit
Digital output short-circuit
Digital input wire break
Digital output wire break
Sensor supply
Number of sensor supplies
Load current
Short-circuit protection
Sensor selection data
Cable length, shielded
Cable length, unshielded
Input voltage
Nominal value
For signal "1"
For signal "0"
Input current
At signal "1"
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
I/O device digital inputs/digital outputs
9.3 I/O device digital inputs/digital outputs
No
No
Yes
Yes
Red/yellow "SF/MT" LED
Red "BF" LED
Green "ON" LED
Green "P1 LK" and "P2 LK" LED; LED for PROFINET IO
infeed and loop-through
Green LED
Red LED
Green LED
Red LED
Yes
Yes
Yes, per channel
Yes, per channel
Yes, input current < 0.3 mA, per channel
Yes, in the off state, per channel
8, 4×1L+ and 4×2L+
Note: The sensor supply is only available when the
corresponding channel is parameterized as an
"Input".
100 mA per output
Yes, electronic
Max. 30 m
Max. 30 m
24 V DC
11 to 30 V
-3 to +5 V
Typ. 7 mA