Siemens SIMATIC Distributed I/O ET 200eco PN Operating Instructions Manual page 163

Hide thumbs Also See for SIMATIC Distributed I/O ET 200eco PN:
Table of Contents

Advertisement

I/O device analog input/analog output
10.1 I/O device analog input
Technical specifications
Voltage
Resistance
Thermoresistor
Thermocouple
Permitted input voltage for voltage input (destruc­
tion limit)
Connection of sensors for RTD
Connection of sensors for thermocouples
Temperature compensation
None
Internal
RTD (0)
Dynamic reference temperature
Fixed reference temperature
Technical unit for temperature measurement
Formation of analog values
Measuring principle
Integration time and conversion time/resolution (per channel)
Integration time parameterizable
Interference frequency suppression in Hz
Integration time in ms
Conversion time in ms (per channel)
Resolution for RTD
(including overrange)
Resolution for thermocouples
(including overrange)
Measured value smoothing
164
1
2
Level
None
Weak
Medium
Strong
±80 mV
150 Ω/10 MΩ
300 Ω/10 MΩ
600 Ω/10 MΩ
3000 Ω/10 MΩ
Pt100/10 MΩ
Pt200/10 MΩ
Pt500/10 MΩ
Pt1000/10 MΩ
Ni100/10 MΩ
Ni120/10 MΩ
Ni200/10 MΩ
Ni500/10 MΩ
Ni1000/10 MΩ
Types N, E, J, K
28.8 V continuous, 35 V for max. duration of
500 ms
Yes (with 2-/3-/4-conductor connection)
Yes
Yes, parameterizable
Yes, parameterizable
Yes, parameterizable
Yes, parameterizable
Yes, parameterizable
°C, °F, K
Integrating
Yes
500/60/50/10
2.0/16.667/20/100
4/19/22/102
150 Ω, 300 Ω, 600 Ω, 3000 Ω/15 bits
Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200,
Ni500, Ni1000/15 bits + sign
Types N, E, J, K/15 bits + sign
Yes, parameterizable in 4 levels
Time constant
1 x cycle time
4 x cycle time
16 x cycle time
64 x cycle time
Operating Instructions, 06/2022, A5E01250250-AN
ET 200eco PN

Advertisement

Table of Contents
loading

Table of Contents