Siemens SIMATIC Distributed I/O ET 200eco PN Operating Instructions Manual page 192

Hide thumbs Also See for SIMATIC Distributed I/O ET 200eco PN:
Table of Contents

Advertisement

Technical specifications
Operational limit (across the temperature range,
relative to output range)
Basic error limit (operational limit at 25°C, relative
to output range)
Temperature error (relative to output range)
Linearity error (relative to output range)
Repeat accuracy (in steady-state condition at 25°C,
relative to output range)
Output ripple (relative to output range, bandwidth
0 to 50 kHz
Status, interrupts, diagnostics
Interrupts
Diagnostics functions
Group error/maintenance
Bus monitoring PROFINET IO
Monitoring of supply voltage 1L+
Existing connection to network
Fault at analog output
Diagnostic information can be read
Monitoring for
Supply voltage 1L+
Sensor supply short-circuit
Short-circuit
Wire break
Thermal overload at output
Insulation
Insulation test voltage
Ethernet interface
All other circuit elements
Electrical isolation
Between 1L+ and 2L+
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
I/O device analog input/analog output
10.2 I/O device analog output
Ambient temperature
positive
negative
(0 °C to
-25 °C)
U
0.1%
0.15%
I
0.15%
0.25%
U
0.08%
I
0.1%
Ambient temperature
positive
U
0.001%/K
I
0.0025%/K
± 0.02%
±0.008%
U
±0.6 mVrms
I
±0.4 nArms
Yes
Red/yellow "SF/MT" LED
Red "BF" LED
Green "ON" LED
Green "P1 LK" and "P2 LK" LED; LED for PROFINET
IO infeed and loop-through
Red LED
Yes
Yes
Yes
Yes; channel (voltage)
Yes; channel (current)
Yes; channel
1500 V
(IEEE802.3, Type Test)
rms
707 V DC (type test)
Yes
negative
(-25 °C to
-40 °C)
0.3%
0.4%
negative
0.003%/K
0.005%/K
193

Advertisement

Table of Contents
loading