Pin assignment
The tables below show the pin assignments.
Pin
1
2
3
4
5
Table 3-26  Pin assignment of the M12 cable connector at the current output
Pin
1
2
3
4
5
Information on wiring
• If you are wiring your configuration, you must take into account the impact of cable
length on the supply voltage to the ET 200eco PN (permitted tolerance).
• The maximum input current of the voltage distributor is 8 A for 1L+ non-switched and 2L+
switched.
Do not exceed these values.
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Assignment of X05
Ground 2M (switched)
Ground 1M (non-switched)
Functional earth FE
24 V (1L+ non-switched)
24 V (2L+ switched)
Assignment of X01 to X04
24 V (1L+ non-switched)
Ground 2M (switched)
Ground 1M (non-switched)
24 V (2L+ switched)
Not used
CAUTION
Adhering to the maximum infeed currents and cable cross-sections
If you do not adhere to the maximum infeed currents and the cable cross-sections
required for these currents, you will risk overheating the cable insulation and contacts
resulting in damage to the device.
3.8 Wiring the voltage distributor
View of the 7/8" cable connector (24 V con­
nection)
View of the M12 cable connector
Wiring