Configuring

4.9 Reset to factory settings (PROFINET)

Detailed information
For further information, see the SIMATIC PROFINET system description
(http://support.automation.siemens.com/WW/view/en/19292127) System Manual and the
Migration from PROFIBUS DP to PROFINET IO
(http://support.automation.siemens.com/WW/view/en/19289930) Programming Manual.
4.8

Media redundancy

Media redundancy
Function for ensuring the network and system availability. Redundant transmission links (ring
topology) ensures that an alternative communication path is made available if a transmission
link fails (starting with STEP 7 V5.5) (not for 6ES7148-6JA00-0AB0 IO-Link Master up to
firmware version 6.x).
For additional information, refer to the STEP 7 online help and the SIMATIC PROFINET system
description (http://support.automation.siemens.com/WW/view/en/19292127) manual.
4.9
Reset to factory settings (PROFINET)
Reset to factory settings (PROFINET)
NOTE
The stations of a bus segment can fail during the reset to factory settings.
"Reset to factory settings" is only possible if the IO Device is not exchanging data with a
controller.
SNMP parameters in non-volatile memory are reset to factory settings (STEP 7 V5.3 SP 3 and
higher) in the HW Config dialog PLC > Ethernet > Edit Ethernet Nodes, "Reset" button under
"Reset to factory settings".
The following retentive data are retained during the reset:
• The MAC address,
NOTE
Deleting the device name
The device name is deleted by means of the "Reset to factory settings" function.
• The I&M0 data,
• The settings configured with S7-PCT,
• The outputs take up the configured substitute value behavior.
70
Operating Instructions, 06/2022, A5E01250250-AN
ET 200eco PN