Technical specifications
Interrupts
Diagnostics functions
•
Group error/maintenance
•
Bus monitoring PROFINET IO
•
Monitoring of supply voltage 1L+
•
Existing connection to bus
•
Analog input error
•
Diagnostic information can be read
Monitoring for
•
Sensor supply short-circuit
•
Wire break
•
Underflow and overflow
•
Supply voltage 1L+
Insulation
Insulation test voltage
•
Ethernet interface
•
All other circuit elements
Standards, approvals, certificates
Suitable for applications according to AMS 2750
Suitable for applications according to CQI-9
Electrical isolation
•
Between 1L+ and 2L+
•
Between 1L+, channels and all other circuit ele
ments
•
Between channels
•
Between Ethernet and all other circuit elements Yes
1
"No temperature compensation" is always run when using the measuring type ±80 mV regardless of
the configured temperature compensation.
2
With 3-wire resistance measurement (and thermal resistor) the measuring resistances and the line
resistances are updated in alternating cycles. Rapid changes in the measuring resistance therefore
impair the accuracy.
3
For thermocouples, the information refers to the temperature range from -100 °C to nominal value
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
I/O device analog input/analog output
10.1 I/O device analog input
Yes
Red/yellow "SF/MT" LED
Red "BF" LED
Green "ON" LED
Green "P1 LK" and "P2 LK" LED; LED for PROFINET IO
infeed and loop-through
Red LED
Yes
Yes, only if channel is enabled
4 to 20 mA, 1 to 5 V, resistors and thermoresistors
Yes
Yes
1500 V
(IEEE802.3, Type Test)
rms
707 V DC (type test)
Yes; Declaration of Conformity, see online support
entry 109757262
Yes; based on AMS 2750 E
Yes
No
No
157