10.1.3
Parameter overview analog input
Parameters for analog input 8 AI 4 U/I + 4 RTD/TC 8xM12 (6ES7144-6KD00-0AB0)
Parameters
Group diagnostics
Diagnostics, missing 1L+
Diagnostics, sensor supply
short-circuit
Interference frequency suppres
sion
Temperature unit
Reference temperature for TC
Measurement type, channels 0
to 3
Measurement type, channels 4
to 7
Measurement range, channels
0 to 3
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Range of values
•
Disable
•
Enable
•
Disable
•
Enable
•
Disable
•
Enable
•
Off (Fast Mode)
•
60 Hz
•
50 Hz
•
10 Hz
•
Celsius
•
Fahrenheit
•
Kelvin
•
-145.0 to 155.0 (Celsius)
•
-229.0 to 311.0 (Fahrenheit)
•
128.2 to 428.2 (Kelvin)
•
Disabled
•
Voltage
•
Current (4-wire transducer)
•
Current (2-wire transducer)
•
Disabled
•
Resistance (4-wire connection)
•
Resistance (3-wire connection)
•
Resistance (2-wire connection)
•
Thermoresistor
(linear, 4-conductor connection)
•
Thermoresistor
(linear, 3-conductor connection)
•
Thermoresistor
(linear, 2-conductor connection)
•
Thermocouple elements
•
Voltage +/-80 mV
•
1 to 5 V
•
0 to 10 V
•
+/-10 V
•
0 to 20 mA
•
4 to 20 mA
•
±20 mA
I/O device analog input/analog output
10.1 I/O device analog input
Default setting
Range of effectiveness
Disable
Device
Disable
Device
Disable
Device
50 Hz
Device
Celsius
Channel groups 4 to 7
0.0
Device
Voltage
Channel
Thermoresistor Pt100
Channel
(4-conductor connec
tion)
±10 V
Channel
167