I/O device analog input/analog output
10.1 I/O device analog input
Technical specifications
Supported Ethernet services
PROFINET interface
•
Connection socket
•
Switch function
•
Auto-crossover
Manufacturer ID (Vendor ID)
Device ID (DeviceID)
Voltages and currents
Supply voltage 1L+
Reverse polarity protection
•
Infeed current 1L+
Supply voltage 2L+
•
Infeed current 2L+
Current consumption
•
From supply voltage 1L+
•
From supply voltage 2L+
Power loss of the device
Analog inputs
Number of inputs
Cable length, shielded
Sensor supply
Number of sensor supplies
Total current
Short-circuit protection
•
Response threshold
Sensor selection data
Input ranges (Rated value)/input resistance or input voltage
•
Voltage
154
PROFINET IO (Device)
•
ping
•
arp
•
LLDP
•
Network diagnostics (SNMP)
•
DCP
•
Prioritized startup
•
Media redundancy
2 x M12 d-coded
Yes, internal
Yes; if autonegotiation is enabled
002A
H
0306
H
DC 24 V
Yes; against destruction
Max. 4 A
DC 24 V
Max. 4 A
Typ. 110 mA
0 mA
Typ. 2.8 W, without sensor current
8 (4 for U or I, 4 for RTD or thermocouple)
Max. 30 m
4
Max. 1 A
Yes; electronic, for each module, to ground
Min. 1.4 A
±80 mV/10 MΩ
±10 V/100 kΩ
0 to 10 V/100 kΩ
1 to 5 V/100 kΩ
Operating Instructions, 06/2022, A5E01250250-AN
ET 200eco PN