Output Ranges Of Analog Output Device - Siemens SIMATIC Distributed I/O ET 200eco PN Operating Instructions Manual

Hide thumbs Also See for SIMATIC Distributed I/O ET 200eco PN:
Table of Contents

Advertisement

I/O device analog input/analog output
10.2 I/O device analog output
Type of output
With this parameter, you set the output type, for example, voltage. For any unused channels,
select the disabled setting. For a disabled channel, the conversion time and integration time
of the channel = 0 s, and the cycle time is optimized.
Output range
With this parameter, you set the output range of the selected output type.
Diagnostics, wire break (in current mode)
When this parameter is enabled, the Wire break diagnostics event is generated when a wire
break is detected. This diagnostics event cannot be detected in the zero range.
Diagnostics, short circuit (in voltage mode)
If you enable this parameter, a diagnostics event is generated in the event of a short circuit in
the output line. This diagnostics event cannot be detected in the zero range.
Diagnostics, overload
If you enable this parameter, the diagnostics event is generated in the event of an overload.
Substitute values
With this parameter, you enter a substitute value that the module is to output in CPU-STOP
mode. The substitute value must be in the nominal range, overrange, or underrange.
10.2.4

Output ranges of analog output device

Output ranges for voltage and current: ±10 V; ±20 mA
Output range
Output range
±10 V
0.00 V
0.00 mA
11.76 V
23.52 mA
196
±20 mA
Decimal
32767
32512
32511
27649
Units
Hexadecimal
7FFF
H
7F00
H
7EFF
H
6C01
H
Operating Instructions, 06/2022, A5E01250250-AN
Range
Overflow
Overrange
ET 200eco PN