Pin assignment
The tables below show the pin assignments.
Table 3-23  Pin assignment of the insulation displacement terminal block.
Pin
1
2
3
4
Table 3-24  Pin assignment of the M12 connector
Pin
1
2
3
4
Information on wiring
• If you are wiring your configuration, you must take into account the impact of cable
length on the supply voltage to the ET 200eco PN (permitted tolerance).
• The maximum infeed current of the terminal block is 10 A for 1L+ non-switched and 10 A
for 2L+ switched.
Do not exceed these values.
See also
Installing the terminal block (Page 24)
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Assignment
24 V (1L+ non-switched)
Ground 1M (non-switched)
24 V (2L+ switched)
Ground 2M (switched)
Assignment
24 V (1L+ non-switched)
Ground 2M (switched)
Ground 1M (non-switched)
24 V (2L+ switched)
CAUTION
Adhering to the maximum infeed currents and cable cross-sections
If you do not adhere to the maximum infeed currents and the cable cross-sections
required for these currents, you will risk overheating the cable insulation and contacts
resulting in damage to the device.
3.7 Wiring the terminal block
View of the insulation displacement ter­
minal block:
View of the cable connector
Wiring