Interrupt, error, and system messages
7.5 Diagnostics with STEP 7
Error class
Error text
00110
6
Wire break
B
D
00111
7
Violation of upper
B
D
limit
01000
8
Violation of lower
B
D
limit
01001
9
Error
B
D
10000
16
Parameter assign­
B
D
ment errors
10001
17
1L+ or 2L+ is
B
D
missing
10101
21
Reference chan­
B
D
nel fault
Error classes for IO-Link Master (6ES7148-6JA00-0AB0), Slot 1
Table 7-9  Overview Error types Slot 1
Error class
Error text
00001
1
Short-circuit
B
D
00010
2
Undervoltage
B
D
00100
4
Overload
B
D
00101
5
Overtemperature •
B
D
00110
6
Wire break
B
D
88
Meaning
Signal line to a sensor or actuator inter­
rupted
Sensor or actuator failure
Load impedance too high
The value is above the overrange
Value is below the underrange
Internal I/O device error has occurred
(diagnostic message on channel 0
applies to the whole I/O device).
I/O device is incorrectly parameterized •
Supply voltages missing or too low
Load voltage supply missing or too low
Measurement cable for compensation
interrupted
Data record DS2 incorrect
Timeout for "Dynamic ref. Temp."
Meaning
Short circuit at the process cables of the IO-Link device
(0x5151)
Supply voltage too low (0x5110 to 0x5119)
Overload of the output stage of the IO-Link Devices (0x5410)
Ambient temperature too high (0x4110)
IO-Link Device too hot (0x4210)
IO temperature exceeded (0x4310)
No IO-Link Device connected
Incorrect IO-Link Device connected
Signal cable to IO-Link Device interrupted
Signal cable to IO-Link Device short-circuited
Short-circuit of supply voltage at sensor
IO-Link Device addressed with too short communication
cycle time
IO-Link Device cannot communicate due to another error
(0xFF10)
Remedy
Correct the process wiring
Replace the sensor or actuator
Use a sensor with lower impedance
Use an actuator with lower load imped­
ance
Correct the I/O device to sensor tuning
Modify measuring range by means of
parameter assignment
Correct the I/O device to sensor tuning
Modify measuring range by means of
parameter assignment
Replacement of I/O device
Correct the parameter assignment
Check the supply voltages
Check the load voltage supply
Correct the process wiring
Correct the process wiring
Check the data record DS2.
Send DS2
IO-Link
Master
Operating Instructions, 06/2022, A5E01250250-AN
IO-Link
Device
X
X
X
X
X
ET 200eco PN