I/O device digital inputs/digital outputs
9.1 I/O device digital inputs
Technical data
•
Ethernet interface
•
All other circuit elements
Electrical isolation
•
Between 1L+ and 2L+
•
Between 1L+, channels and all other circuit ele
ments
•
Between channels
•
Between Ethernet and all other circuit elements Yes
Status, interrupts, diagnostics
Interrupts
Diagnostics function
•
Group error/maintenance
•
Bus monitoring PROFINET IO
•
Monitoring of supply voltage 1L+
•
Existing connection to network
•
Digital input
•
Fault at digital input
•
Diagnostic information can be read
Monitoring for
•
Short-circuit
•
Wire break
•
Missing sensor supply
Sensor supply
Number of sensor supplies
Load current
Short-circuit protection
Sensor selection data
Cable length, shielded
Cable length, unshielded
Input voltage
•
Nominal value
•
For signal "1"
•
For signal "0"
Input current
•
At signal "1"
Input delay
•
At "0" to "1"
110
1500 V
(IEEE802.3, Type Test)
rms
707 V DC (type test)
Yes
No
No
Yes
Yes
Red/yellow "SF/MT" LED
Red "BF" LED
Green "ON" LED
Green "P1 LK" and "P2 LK" LED; LED for PROFINET IO
infeed and loop-through
Green LED
Red LED
Yes
Yes, per channel group
Input current < 0.3 mA, per channel
Yes
4
100 mA per output
Yes, electronic
Max. 30 m
Max. 30 m
DC 24 V
11 to 30 V
-3 to +5 V
Typ. 7 mA
Typ. 3 ms
Operating Instructions, 06/2022, A5E01250250-AN
ET 200eco PN