I/O device digital inputs/digital outputs

9.2 I/O device digital outputs

9.2
I/O device digital outputs
9.2.1

I/O device 8 DO DC 24 V/1.3A 4xM12

Article number
6ES7142-6BF00-0AB0
Properties
The 8 DO DC 24V/1,3A 4×M12 I/O device has the following properties:
• 8 digital outputs
• Dimensions 30 x 200 mm and duplicate assignment of the sockets
• Output current: 1.3 A per output
• Rated load voltage DC 24 V
• Suitable for solenoid valves, DC contactors, and indicator lights
• Diagnostics
– "Missing 1L+ or 2L+" for the I/O device
– "Wire break at outputs" per channel
– "Short-circuit to M at outputs" per channel
• Parameterizable response to CPU/Master STOP
• Prioritized startup
• Media redundancy
Pin assignment of the sockets for digital outputs
The table below shows the pin assignment of the four sockets for connecting digital outputs.
Table 9-4  Pin assignment of sockets X1 to X4 for digital outputs
Pin
Socket X1
24 V (1L+ non-switched)
1
2
DQ
4
3
4
DQ
0
5
122
Assignment
Socket X2
Output signal
DQ
5
Ground 1M
Output signal
DQ
1
Functional earth FE
Socket X3
24 V (2L+ switched)
Not used
DQ
6
Ground 2M
DQ
2
Socket X4
DQ
7
DQ
3
Operating Instructions, 06/2022, A5E01250250-AN