Status and error displays SF/MT, BF, ON
Table 7-1 Status and error displays of the ET 200eco PN
LEDs
SF/MT
BF
ON
Off
Off
On
Off
Off
Off
*
Flashing On
*
On
On
On
*
On
(red)
On
*
*
(yellow)
* irrelevant
Status display of the port LEDs
Table 7-2 Status display of the port LEDs
LED
P1 LK
P2 LK
Off
Off
No connection to the switch/IO Controller.
On
On
Connection to switch/IO Controller.
Status display DC 24V (only on I/O devices with digital outputs)
The DC 24V LED is lit in green color to indicate that you have connected the 2L+ switched
load voltage supply. If the LED is not lit, check whether power is switched, or whether the
fuse is okay.
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Meaning
IO Device is currently exchanging data with the
IO Controller without errors. The IO Device is
supplied with power (electronic/sensor supply).
Electronic/sensor voltage missing or too low at
the I/O device.
Hardware fault.
Faulty or no connect message frame - no data
exchange between the IO Controller and the
distributed device (IO Device), although the
device is physically connected to the switch.
Causes:
•
Incorrect device name
•
Error in configuration
•
Parameterization errors
•
The IO Device is not connected to a switch.
Fault in peripheral circuit.
Incoming diagnostics
Maintenance alarm
Meaning
Interrupt, error, and system messages
7.3 Diagnostics by means of LED display
Remedy
---
Switch on the electronic/sensor/load supply for
the IO Device.
Replace the I/O device.
•
Check the I/O device.
•
Check the configuration and parameter set
tings.
•
Check the device name.
•
Check the IO Controller.
•
Connect to the IO Controller.
•
Assign a valid device name to the I/O device.
•
Check the bus installation.
•
Check whether the M12 cable connectors
are properly installed.
•
Check whether the bus cable to the IO Con
troller is interrupted.
Evaluate the diagnostics interrupt.
Analyze the maintenance alarm.
Remedy
Check the IE cable.
-
81