Parameter Description Analog Output - Siemens SIMATIC Distributed I/O ET 200eco PN Operating Instructions Manual

Hide thumbs Also See for SIMATIC Distributed I/O ET 200eco PN:
Table of Contents

Advertisement

Output range
1 to 5 V
0 to 10 V
±10 V
0 to 20 mA
4 to 20 mA
±20 mA
10.2.3

Parameter description analog output

Group diagnostics
You can generally enable and disable the diagnostics function of the device with this
parameter.
The "Fault" and "Parameter assignment error" diagnostics functions are always independent
of the group diagnostics.
Diagnostics, missing 1L+
If you enable this parameter, the check for missing supply voltage is enabled.
Diagnostics, sensor supply short circuit
When this parameter is enabled, the system generates a diagnostics event if it detects a
short-circuit of the sensor supply to ground. This diagnostics function is activated when the
group diagnostics function is enabled.
Response to CPU/Master STOP
Select how the module's outputs will respond to a CPU STOP:
• Shut down
The I/O device goes to the safe state. The process image output is deleted (=0).
• Keep last value
The I/O device retains the last value to be output before STOP.
• Substitute value
The I/O device outputs the value for the channel set beforehand.
NOTE
Make sure that the plant is always in a safe state if "Keep last value" is selected.
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Permitted substitute value
0.000 V to 5.704 V
0.000 V to 11.759 V
-11.759 V to 11.759 V
0.000 mA to 23.518 mA
0.000 mA to 22.814 mA
-23.519 mA to 23.518 mA
I/O device analog input/analog output
10.2 I/O device analog output
195