Mitsubishi Electric MELSERVO-J3 Series Instruction Manual page 655

Hide thumbs Also See for MELSERVO-J3 Series:
Table of Contents

Advertisement

16. INDEXER POSITIONING OPERATION
No.
Symbol
PD24 *DOP5 Function selection D-5
Select the output status of the warning (RXnA).
0 0
Setting
0
1
Note. 0: OFF
1: ON
CC-Link communication error (A8D) detection time
PD25
A8DT
When the "CC-Link communication error (A8D) detection delay" is selected with
parameter No.PC50, this parameter is valid.
If parameter No.PC50 is "0000h", it is 10ms.
Convert a decimal value to a hexadecimal value for input.
The setting range is up to 1000 ms. A set value is limited within the setting range.
For example) If "03E8h" is set, the set value becomes 1000ms.
The converted decimal value of "1388h" is 10000ms, but it is limited to 1000ms,
which is the upper limit of the setting range.
CAUTION
This parameter is available with servo amplifiers with software version A8 or later.
When this parameter is set using MR Configurator with software version C5 or
earlier, the parameter name is not displayed. However, the setting value is
changeable. Follow the instructions in this Instruction Manual to set the value.
PD26
TLT
Indexer positioning operation torque limit delay time
Set the delay time from when the in position (RXn1) turns on until the internal
torque limit 2 (parameter No.PC35) becomes effective.
Set the delay time after converting it into hexadecimal. The setting range is from 0
to 1000 ms.
PD27
For manufacturer setting
PD28
Do not change this value by any means.
PD29
PD30
Name and function
0
Selection of output device at warning occurrence
Select the warning (RXnA) and trouble (RX(n 1)A or
RX(n 3)A) output status at warning occurrence.
(Note) Device status
RXnA
RX of
RX(n+1)A or
CC-Link
RX(n+3)A
Output
ALM
device
RXnA
RX of
RX(n+1)A or
CC-Link
RX(n+3)A
Output
ALM
device
If CC-Link communication error
(A8D) does not have to be
detected, use the
communication time-out
detection time in the initial
setting. When you change the
setting value, do not set an
unnecessarily long time period.
Doing so interferes swift stop
operation at an occurrence of
CC-Link communication error
(A8D).
1
0
1
0
ON
OFF
Warning
occurred.
1
0
1
0
ON
OFF
Warning
occurred.
16 - 100
Initial
Setting
Unit
value
Range
0000h
0000h
ms
0000h
to
03E8h
0064h
ms
Refer to
name and
function
column.
0000h
0000h
0000h
0000h

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents