16. INDEXER POSITIONING OPERATION
No.
Symbol
PC13
Not used in indexer positioning operation.
Do not change the parameter.
PC14
*BKC
Backlash compensation
Used to set the backlash compensation made when the command
direction is reversed.
This function compensates for the number of backlash pulses in the
opposite direction to the home position return direction.
For the home position ignorance (servo-on position as home position), this
function compensates for the number of backlash pulses in the opposite
direction to the first rotating direction after establishing the home position
by switching ON the servo-on (RYn0).
In the absolute position detection system, this function compensates for
the backlash pulse count in the direction opposite to the operating direction
at power-on.
PC15
For manufacturer setting
Do not change this value by any means.
PC16
MBR
Electromagnetic brake sequence output
Used to set the delay time (Tb) between when the electromagnetic brake
interlock (MBR) switches off and when the base circuit is shut off.
PC17
Not used in indexer positioning operation.
Do not change the parameter.
PC18
*BPS
Alarm history clear
Used to clear the alarm history.
0 0 0
PC19 *ENRS Encoder output pulse selection
Use to select the encoder output pulse direction and encoder output pulse
setting.
0 0
Setting
0
1
Encoder output pulse setting selection (refer to parameter No.PA15).
0: Output pulse designation
1: Division ratio setting
2: Outputs the encoder pulse without processing it.
Name and function
Alarm history clear
0: Invalid
1: Valid
When alarm history clear is made valid,
the alarm history is cleared at next power-on.
After the alarm history is cleared, the setting
is automatically made invalid (reset to 0).
Encoder output pulse phase changing
Changes the phases of A, B-phase encoder output
pulses.
Servo motor rotation direction
CCW
A-phase
A-phase
B-phase
B-phase
A-phase
A-phase
B-phase
B-phase
CW
16 - 92
Initial value
Unit
Setting range
0
0
pulse
0000h
100
ms
50
0000h
name and
0000h
name and
0
to
32000
0
to
1000
Refer to
function
column.
Refer to
function
column.