M40e Router Installation Safety Guidelines and Warnings

234
All manuals and user guides at all-guides.com
Fire Suppression
In the event of an electrical hazard or an electrical fire, first turn power off to the equipment
at the source. Then use a Type C fire extinguisher, which uses noncorrosive fire retardants,
to extinguish the fire. For more information about fire extinguishers, see "Fire Suppression
Equipment" on page 234.
Fire Suppression Equipment
Type C fire extinguishers, which use noncorrosive fire retardants such as carbon dioxide
(CO
) and Halotron, are most effective for suppressing electrical fires. Type C fire
2
extinguishers displace the oxygen from the point of combustion to eliminate the fire. For
extinguishing fire on or around equipment that draws air from the environment for cooling,
use this type of inert oxygen displacement extinguisher instead of an extinguisher that
leave residues on equipment.
Do not use multipurpose Type ABC chemical fire extinguishers (dry chemical fire
extinguishers) near Juniper Networks equipment. The primary ingredient in these fire
extinguishers is monoammonium phosphate, which is very sticky and difficult to clean.
In addition, in minute amounts of moisture, monoammonium phosphate can become
highly corrosive and corrodes most metals.
Any equipment in a room in which a chemical fire extinguisher has been discharged is
subject to premature failure and unreliable operation. The equipment is considered to
be irreparably damaged.
NOTE: To keep warranties effective, do not use a dry chemical fire extinguisher
to control a fire at or near a Juniper Networks router. If a dry chemical fire
extinguisher is used, the unit is no longer eligible for coverage under a service
agreement.
We recommend that you dispose of any irreparably damaged equipment in an
environmentally responsible manner.
General Safety Guidelines for M Series, MX Series, and T Series Routers
General Safety Warnings for M Series, MX Series, and T Series Routers
General Electrical Safety Warnings for M Series, MX Series, and T Series Routers
DC Power Electrical Safety Warnings for M Series, MX Series, and T Series Routers
M40e Chassis Lifting Guidelines on page 235
Installation Instructions Power Warning for M Series, MX Series, and T Series
Routers on page 235
Rack-Mounting Requirements and Warnings for M Series, MX Series, and T Series
Routers on page 236
Ramp Warning for M Series, MX Series, and T Series Routers on page 240
Copyright © 2010, Juniper Networks, Inc.

Advertisement

Table of Contents
loading

Table of Contents