1 Introduction
SNMP
EtherNet/IP conformance test
Ethernet interface
Applicable CPU Units
Unit current consumption
Weight
Dimensions
*1 If tag data links are being used, use 100Base-TX.
*2 Here, pps means "packets per second" and indicates the number of packets that can be processed in one sec-
ond.
*3 To use a data size of 505 bytes or higher, the system must support a large forward open (an optional CIP spec-
ification). The CS/CJ-series Units support a large forward open, but before connecting to nodes of other com-
panies, confirm that those devices also support it.
*4 If the parameters of the EtherNet/IP Unit are changed, the Unit is restarted. When other nodes are in commu-
nications with the affected node, the communications will temporarily time out and automatically recover later.
*5 Because the EtherNet/IP Unit is equipped with an IGMP client (version 2), unnecessary multicast packets can
be filtered by an Ethernet switch that supports IGMP snooping.
*6 The EtherNet/IP Unit uses the TCP/UDP port numbers shown in the following table.
Do not set the same port number for more than one TCP/UDP service.
Service
EIP data links
Used by system
CIP messages
FTP client data transfer port
DNS client
BOOTP client
FTP client control port
SNTP client
SNMP agent
SNMP trap
*7 A CPU Unit with unit version 1.01 or later and Sysmac Studio version 1.02 or higher are required to use CPU
routing.
1-8
Item
Agents
MIB
Protocol
UDP
UDP
TCP
TCP
TCP/UDP
UDP
TCP
UDP
UDP
UDP
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Specifications
SNMPv1 or SNMPv2c
MIB-II
Conforms to A8
10Base-T or 100Base-TX
Auto negotiation or fixed settings
NJ301-@@@@ CPU Units (unit version 1.01 or later)
NJ501-@@@@ CPU Units (unit version 1.01 or later)
5 VDC 410 mA max.
94 g max.
31 × 90 × 65 mm (W × H × D)
Port number
2222
Fixed values
2223, 2224
44818
20
53
68
21
You can change the port number in
the Unit Settings on the Sysmac
123
Studio.
161
162
Remarks