13 Troubleshooting
Event code
Event name
84E10000 hex
BOOTP
Server Error
54AF 0000 hex
Access
Detected
Outside
Range of
Variable
84E20000 hex
Link OFF
Error
13-34
Meaning
Assumed cause
Connection with the
• Server setting error (The
BOOTP server
acquired IP address is illegal.)
failed.
• Server is down.
• An error occurred in the com-
munications path.
Accessing a value
• An out-of-range value was writ-
that is out of range
ten by an EtherNet/IP tag data
was detected for a
link for a variable with a speci-
tag variable that is
fied range. A value that does
used in a tag data
not specify an enumerator was
link.
written by an EtherNet/IP tag
data link for an enumeration
variable.
The Ethernet link
• The Ethernet cable is discon-
status turned OFF.
nected.
• An Ethernet cable is discon-
nected or loose.
• The switching hub power sup-
ply is turned OFF.
• Baud rate mismatch.
• Noise
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Level
Maj
Prt
Min
Obs Info
S
page 13-46
S
page 13-46
U
S
page 13-47
Reference