• You can use MC − MCR instructions and JMP instructions to process data only when the data
links are operating normally as shown below.
Node A data link
normal operation flag
Node B data link
normal operation flag
Node C data link
normal operation flag
Precautions for Correct Use
Precautions for Correct Use
Even if an error occurs in communications with a target device, the input data from the target
device will remain stored in words allocated in memory to the local node. To prevent malfunc-
tions, write the user program so that no input processing is performed when the following Unit
Error Occurred (*_UnitErr) are TRUE.
7-72
MC
Node A data processing
MCR
MC
Node B data processing
MCR
MC
Node C data processing
MCR
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)