Omron CJ1W-EIP21 Operation Manuals page 235

For nj-series cpu unit. cj-series ethernet/ip units
Hide thumbs Also See for CJ1W-EIP21:
Table of Contents

Advertisement

General sta-
tus code (hex)
21
22
23 and 24
25
26
27
28
29
2A
2B to CF
D0 to FF
 Examples of Additional Status When General Status Is 01 Hex
(Status of Connection Manager Object)
General Sta-
tus (hex)
01
01
01
01
01
01
01
01
01
01
01
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Status name
Write-once value or medium
already written
Invalid Reply Received
Key Failure in path
Path Size Invalid
Unexpected attribute in list
Invalid Member ID
Member not settable
Group 2 only server general fail-
ure
Reserved for Object Class and
service errors
Additional Status (hex)
0100
0103
0106
0107
0108
0109
0100
0111
0113
0114
0115
8 Message Communications
Description of status
An attempt was made to write to a write-once medium
(e.g. WORM drive or PROM) that was previously written or
cannot be changed.
An invalid reply was received. (For example, the reply ser-
vice code does not match the request service code, or the
reply message is shorter than the minimum expected
reply size.) This status code is used for other causes of
invalid replies.
Reserved by CIP for future extensions.
The key segment that was included as the first segment in
the path does not match the destination module. The
object specific status must indicate which part of the key
check failed.
The size of the path that was sent with the service request
is either too large or too small for the request to be routed
to an object.
An attempt was made to set an attribute that is not able to
be set at this time.
The member ID specified in the request does not exist in
the specified class, instance, and attribute.
A request to modify a non-modifiable member was
received.
This error code is reported only by group 2 only servers
with 4K or less of code space and only in place of Service
not supported, Attribute not supported, or Attribute not
settable.
Reserved by CIP for future extensions.
This range of error codes is to be used to indicate object
class-specific errors. This code range is used only when
none of the error codes in this table accurately reflect the
error that occurred. The additional code field is used to
describe the general error code in more detail.
Description
Connection in use or duplicate forward open.
Transport class and trigger combination not supported.
Ownership conflict.
Connection not found at target application.
Invalid connection type. There is a problem with either the
connection type or priority of the connection.
Invalid connection size.
Device not configured.
RPI not supported. May also indicate problem with con-
nection time-out multiplier, or production inhibit time.
Connection Manager cannot support any more connec-
tions.
Either the vendor ID or the product code in the key seg-
ment does not match the device.
Device type in the key segment does not match the device.
8
8-29