7 Tag Data Link Functions
 Example
In the following example, input tags a to g at the originator are a tag set named SP1_IN and output
tags i and ii are a tag set named SP1_OUT. A connection is set between these two tag sets.
Originator device
Connection information
· Target IP address: N
· Originator tag set: SP1_IN
· Target tag set: SP1_OUT
· Packet interval (RPI)
Tag set name: SP1_IN
Controller status
Tag a
Tag b
Tag c
Tag g
There are both input (consume) and output (produce) tag sets. Each tag set can contain only input
tags or only output tags. The same input tag cannot be included in more than one input tag set.
7-4
Tag Set (Inputs)
Connection
EtherNet/IP
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Target Device
IP address: N
Tag Set (Outputs)
Tag set name: SP1_OUT
Controller status
Tag i
Tag ii