Omron CJ1W-EIP21 Operation Manuals page 347

For nj-series cpu unit. cj-series ethernet/ip units
Hide thumbs Also See for CJ1W-EIP21:
Table of Contents

Advertisement

Error
code
(hex)
03C3
FINS/UDP packet discarded
03C4
Server connection error
03C6
Clock write error
03D0
Ethernet basic setting error
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Error
00 hex
00 hex: DNS
03 hex: SNTP
04 hex: FTP
06 hex: BOOTP
07 hex: SNMP
08 hex: SNMP Trap
0001: The clock time
could not be updated
because a error occurred
in the CPU Unit.
0002: The clock time
could not be updated
because the CPU Unit or
operating mode does not
support this function.
01 hex: Ethernet setting
error
02 hex: TCP/IP basic set-
ting error
Detail code
First byte
Second byte
01 to FE hex:
Source node address
01 hex: Specified host
does not exist
02 hex: No such service at
specified host
03 hex: Timeout
06 hex: Host name resolu-
tion error
07 hex: Transmission error
08 hex: Reception error
09 hex: Other error
0A hex: Obtaining IP
address error
Clear the error from the
CPU Unit.
Refer to Section 12 Com-
munications Performance
and Communications
Load and check the appli-
cation conditions.
01 hex: Checksum error
11 hex: Inconsistent set-
tings
12 hex: Specified baud
rate is not supported.
01 hex: Checksum error
11 hex: Invalid IP address
12 hex: Invalid subnet
mask
13 hex: Invalid default
gateway address
14 hex: Invalid primary
name server
15 hex: Invalid secondary
name server
16 hex: Invalid domain
name
17 hex: Invalid host name
13 Troubleshooting
Saved in
non-volatile
memory
No
No
No
Yes
13-29
13