5 Sysmac Studio Settings for the EtherNet/IP Unit
• Class-E IP addresses (240.0.0.0 to 255.255.255.255)
 IP Router Table
Setting
Destination IP address
Gateway address
Additional Information
IP Router Table Setting Example
Set the following IP router table in node A to use tag data links or CIP message communications
between node A and node B through the IP router. When you set the IP router table, node A
sends packets to the gateway IP address (130.25.36.253) if communications instructions are
executed on node A and addressed to node B.
Node A
5-4
Set these settings when the EtherNet/IP Unit communicates with nodes on
other IP network segments via an IP router.
You can set up to eight combinations of IP addresses and gateway
addresses.
Specify 0 for the host portions of the IP addresses.
Refer to the following section for a setting example for the IP router table.
130. 25. XX. XX
130.25.36.253
The host fields are set to 0 in the destination IP address.
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Description
130. 26. XX. XX
130.26.2.254
IP router
Default